AMMONIA GAS DETECTOR
AD-12
CONNECTS TO ALARM CONTROL PANELS
TWO RELAYS AT TWO LEVELS OF DETECTION
WIDE POWER SUPPLY RANGE: 10 to 26 Vac or Vdc
EXPLOSION PROOF DESIGN: IGNITION PROTECTED
WIDE OPERATING TEMPERATURE RANGE: -40 to 100¡F
MAINTENANCE FREE ELECTRONIC SENSOR, SUPERVISED
SMALL, COMPACT, MOUNTS ON 4 X 4 ELECTRICAL BOX
STANDARD CALIBRATION: 25 & 100 ppm (Parts Per Million)
SPECIAL CALIBRATIONS ARE AVAILABLE
SPECIFICATIONS
SIZE: 41/2x41/2x2inches
SHIPPING: one pound
VOLTAGE: 10 to 26 VAC or VDC
POWER: 1.0 VA
COLOR: white
ALARM SET POINT: 25 & 100 ppm Ammonia
RELAY MAX RATING 1 Amp, 125 V, 30VA
RELAY TIME DELAY One minute
RELAY CONTACTS: Two, dry, SPDT
OPERATING TEMP. RANGE: -40° to 100° F
DETECTOR SPACING: 30 feet, 900 sqaure feet
CONNECTIONS: 8 @ number 20 wires
RESPONSE TIME: 3 minutes
INTERFERENCES
When the AD-12 is set to 100 ppm, the following approx. gas
levels can cause an alarm:
NATURAL (METHANE): 10,000 ppm
PROPANE, BUTANE, LP: 4000 ppm
CARBON MONOXIDE: 600 ppm
HYDROGEN: 100 ppm
ETHYLENE OXIDE: 100 ppm
REFRIGERANT R-11: 10,000 ppm
REFRIGERANT R-12: 10,000 ppm
REFRIGERANT R-22: 1000 ppm
REFRIGERANT R-502: 1000 ppm
NOTE: Ammonia is lighter than air: Mount AD-1 high.
OPTION: AD-12-H detector with an operating temperature range of 0 to 150°F.
Manufacured By: Macurco Inc.
Distributed By Engwald

|
|