AMMONIA GAS DETECTOR
AD-1
WIDE OPERATING TEMPERATURE RANGE: -40 TO 100¡F
ELECTRONIC SENSOR: NO MAINTENANCE REQUIRED
ADJUSTABLE SET POINT: 25 TO 275 PPM AMMONIA
WIDE POWER SUPPLY RANGE: 10 TO 26 VAC OR VDC
SIMPLE INSTALLATION AND OPERATION
CONNECTS TO CLASS A & B PANELS
FAIL SAFE SYSTEM EXPLOSION PROOF DESIGN: IGNITION PROTECTED
COST EFFECTIVE
SPECIFICATIONS
SIZE: 41/2x41/2x2inches
SHIPPING: one pound
VOLTAGE: 10 to 26 VAC or VDC
CURRENT DRAW: 83ma @ 12V, 4lma @ 24V
SENSOR MAINTENANCE: none required
COLOR: white
ALARM SET POINT: 25 to 275 ppm Ammonia
AD-1 TEMPERATURE RANGE: -40 to 100¡F
AD-1-H TEMPERATURE RANGE: 0 to 150¡F
RELAY: 1A, i25V, 3OVA, SPDT, Dry Contacts
RESPONSE TIME: 3 minutes
SENSOR LIFE: 7 to 10 years
INTERFERENCES
When the AD-1 is set to 100 ppm, the following approx. gas
levels can cause an alarm:
NATURAL (METHANE): 10,000 ppm
PROPANE, BUTANE, LP: 4000 ppm
CARBON MONOXIDE: 600 ppm
HYDROGEN: 100 ppm
ETHYLENE OXIDE: 100 ppm
REFRIGERANT R-11: 10,000 ppm
REFRIGERANT R-12: 10,000 ppm
REFRIGERANT R-22: 1000 ppm
REFRIGERANT R-502: 1000 ppm
NOTE: Ammonia is lighter than air: Mount AD-1 high.
OPTION: AD-1-H detector with an operating temperature range of 0 to 150°F.
Manufacured By: Macurco Inc.
Distributed By Engwald

|
|